Aguato

    Water treatment

    Maintaining Heat Pump Efficiency at Iberostar Selection Andalucía Playa

    Technologies

    • Sidon Water Integro

    The problem

    The Iberostar Selection Andalucía Playa hotel uses Mitsubishi Q-ton heat pumps for domestic hot water (DHW) generation. This system is highly efficient and designed for thermal energy applications. However, the hotel’s water supply posed a significant challenge: Maximum recommended water hardness for Q-ton: 8.9°F (French degrees) | 5°dH (German degrees) | 89.5 ppm Actual water hardness at the hotel: 18°F (French degrees) | 10°dH (German degrees) | 180 ppm This level exceeds the manufacturer’s recommendation by a factor of two, creating risks such as: Limescale buildup – Scaling in the heat exchanger and water pathways, reducing efficiency. Efficiency loss – Decline in the Coefficient of Performance (COP) due to impaired heat transfer. Increased maintenance needs – More frequent descaling, higher operating costs, and potential system failures.

    Results

    • Results After One Year of Operation
    • The heat pump’s efficiency and operational performance were closely monitored throughout 2024, yielding outstanding results:
    • Performance Metrics
    • - Thermal energy output: 243.94 MWh
    • - Electrical energy consumption: 63,788.6 kWh
    • - Measured COP: 3.83 (very close to the system’s design performance of ~4)
    • Key Findings
    • - Sustained efficiency – The heat pump maintained an optimal COP despite operating in water exceeding its recommended hardness limit.
    • - No scaling observed – The heat exchangers and water pathways remained free of limescale, preserving system efficiency.
    • - Minimal maintenance required – No descaling was needed, reducing downtime and operational costs.
    • Conclusion
    • By integrating the Sidon Water Integro™ system, Iberostar Selection Andalucía Playa successfully preserved the performance of its Mitsubishi Q-ton heat pumps, avoiding efficiency losses and costly maintenance in a high-hardness water environment.
    • This case study highlights how proactive water treatment solutions can protect commercial heat pump systems, ensuring long-term efficiency, reliability, and cost savings—a critical consideration for hotels and other high-demand facilities.

    Photos

    Maintaining Heat Pump Efficiency at Iberostar Selection Andalucía Playa
    Maintaining Heat Pump Efficiency at Iberostar Selection Andalucía Playa, photo 2